How does a brine chiller work?

How does a brine chiller work?

Hiver HBS, HBD & HBM series brine chillers are a solution when cooling medium is water with glycol and this occurs when low fluid temperature is demanded or glycol must be added to the cooling water in order to protect it from freezing. Our systems provide constant supply of chilled propylene glycol from -250C / +250C.

What is chiller flow rate?

Chiller design flow rate is 1.5 gpm per ton [0.027 L/s per kWr] and the minimum is 1.2 gpm per ton [0.022 L/s per kWr]. This means the flow rate can only be reduced 20 percent before reaching minimum. That’s not much for a system that is supposed to be variable primary flow.

How is brine chiller capacity calculated?

Divide Q (BTUs per hour) by 12,000 (the number of BTUs in one ton of cooling capacity). This yields the chiller capacity required to handle the process heat load in tons per hour: Example: 240,000/12,000= 20 tons/hr.

How is evaporator flow rate calculated?

Chilled Water Systems

  1. Total Heat Removed. The total heat removed by an air condition chilled-water system can be calculated. h = 500 q dt (1) where.
  2. Evaporator Flow Rate. The evaporator water flow rate can be calculated. qe = htons 24 / dt (2) where.
  3. Condenser Flow Rate. The condenser water flow rate: qc = htons 30 / dt (3)

How does an air cooled chiller work?

An air-cooled chiller works by absorbing the heat from processed water. Once the water in the air handler system is used, it becomes warm and is sent back to the chiller. Heat is transferred away from the water using the chiller’s evaporator.

What is the pH of brine?

Brine indicates a highly concentrated solution of sodium chloride. Since (NaCl) comes from a strong acid (HCl) & a strong base (NaOH) through a neutralization reaction, then an aqueous solution of this salt will be neutral with a pH=7 whatever the concentration is i.e. 0.2 Molar, 0.4 Molar, 0.5 Molar …etc.

What is flow switch in chiller?

Flow switches monitoring chiller input lines provide the most direct method for proving water flow and protecting chillers from costly freeze damage due to reduced flow and/or fluid loss. The relay output from a flow switch can shut down the chiller to prevent costly repairs.

How many BTU is 160 square feet?

5,000 BTU
How Many Square Feet Will 4,000 – 80,000 BTU Heat?

Heating Capacity Square Footage(Hot Climate) Square Footage(Cold Climate)
4,000 BTU 130 sq ft 70 sq ft
5,000 BTU 160 sq ft 90 sq ft
6,000 BTU 200 sq ft 105 sq ft
9,000 BTU 300 sq ft 160 sq ft

What is TR capacity?

Ton of Refrigeration (TR): Ton of Refrigeration (abbreviated as TR) is an important historical unit of refrigeration capacity. American Society of Heating, Refrigerating and Airconditioning Engineers (ASHRAE) defines 1 TR as equivalent to a refrigeration capacity of 3516.85 W or 3023.95 kcal/h.

How do you calculate gpm of a chiller?

The GPM formula is GPM = Air side Btu ÷ (measured water Δt x 500).

Who is the manufacturer of the brine chiller?

Brine chiller is one kind of low-temperature chillers or low-temperature cooling system specially designed and manufactured for cooling brine. TopChiller® is a professional brine chiller supplier and manufacturer with over 20 years of experience.

What does brine do in a refrigeration system?

In brine chiller circulation, brine works as a common fluid used in large chiller or refrigeration system installations for the transport of heat from place to place.

How are air cooled scroll chillers energy efficient?

The Air-cooled Scroll Chillers are highly energy efficient and are perfectly designed to work within extreme tropical weather conditions. Supported with European origin compressors, these chillers are designed, manufactured and tested in conformation with international industrial standards.

How are water chillers used to cool buildings?

Chillers make cold water or water/glycol fluid mixture in order to cool buildings or processes. Often used in conjunction with coils in air handlers, chillers receive warm fluid from the air handler coil or process load, lower the temperature of the fluid, then a pump returns the fluid to the air handler coil or process.

Posted In Q&A